APCSMART(8) NUT Manual APCSMART(8)NAMEapcsmart - Driver for American Power Conversion Smart Protocol UPS
equipment
SYNOPSISapcsmart-h
apcsmart-a UPS_NAME [-x option=value ...]
Note
This man page only documents the hardware-specific features of the
apcsmart driver. For information about the core driver, see
nutupsdrv(8).
SUPPORTED HARDWARE
The apcsmart driver should recognize (or at the very least, work with)
the majority of Smart-UPS models - which includes Smart-UPS, Matrix-UPS
and Back-UPS lineups, among few other ones.
Currently, we can roughly divide APC hardware into four groups (note
that the division isn’t strict by any means, and the borders between
those are pretty fuzzy):
[very] "old" models
These models usually have old APC logo, white color and no
programmable EEPROM; you won’t find them listed anywhere on APC’s
site either. The support for those will be usually based on
driver’s compatibility tables, or if the model (firmware) is not
listed in those - the driver will try to follow the very basic
subset of features, while still trying to remain useful. Despite
"smart" tagname, they often tend to behave in pretty dumb way (see
the section below about shutdown behaviour).
Example models:
· Smart-UPS 2000I
· Smart-UPS 900I
"new" models
These models usually come from late 1990s / pre-2009 times. They
are often referred as "3rd. gen". For the most part, they have
programmable EEPROM, report supported commands and capabilites, and
should work just fine with the apcsmart driver.
"microlink" models
WARNING: these are not natively supported by apcsmart (or apcupsd,
for that matter, if you’re wondering). Around 2007, APC (now APC
Schneider) decided to go back to its proprietry roots, and all the
new models (SMT, SMX, SURTD) use completely different protocol and
cables. If you purchased a new APC UPS - that uses cable with RJ45
on the one end, and DB-9 on the other - then you have such model.
Your only option to support it through NUT is to purchase a "legacy
communications card" - part #AP9620 (google 'AP9620' for more
details). Or if that’s not an option, rely on official software.
Microsol models
Several Microsol serial models sold in Brazil have been rebranded
as APC Back-UPS, and the model numbers tend to start with "BZ". If
you have one of these "Nobreaks", they will not work with the
apcsmart driver - please see the solis(8) driver instead.
Example models:
· Back-UPS BZ1200-BR
· Back-UPS BZ2200BI-BR
Another thing to remember is that Smart protocol is not USB protocol.
If you have UPS with both USB and serial ports, then depending on how
you connect it, you will need either apcsmart or usbhid-ups driver.
CABLING
This driver expects to see a 940-0024C cable or a clone by default. You
can switch to the 940-0095B dual-mode cable support with the 'cable='
definition described below.
If your 940-xx24X cable is broken or missing, use this diagram to build
a clone:
http://www.networkupstools.org/cables.html#_940_0024c_clone
Note
The "xx" is either "00" for a short cable, or the number of feet of
a longer cable. The "X" is a letter representing the minor revision
of the physical cable and its connectors ("C" and "E" are commonly
found revisions). All minor revisions should use the same pin-outs
and wiring.
You can specify alternate cable in ups.conf(5):
cable=940-0095B
Alternatively, you can also provide it on the command line using:
-x cable=940-0095B
TTY MODES
By default the driver works in canonical mode, but it proved to be a
problem in Windows systems. Furthermore there’s a possibility of some
obscure serial cards or serial-USB converters that could cause problems
as well. You can use 'ttymode=' option to force non-canonical
discipline in ups.conf(5):
ttymode=raw
Alternatively, you can also provide it on the command line using:
-x ttymode=raw
Note
Any other value will make the driver work in the canonical mode.
EXPLANATION OF SHUTDOWN METHODS SUPPORTED BY APC UPSES
APC hardware supports a lot of shutdown methods, that themselves can
differ in behaviour quite a bit, depending on the model.
S (soft hibernate)
This is most basic command present in probably all APC models. It
will hibernate the UPS, and subsequently wake it up when the mains
supply returns. The command doesn’t work if the UPS is running on
mains.
"old" models
The behaviour here is unfortunately pretty primitive - when the
power returns, the UPS just wakes up. No grace periods, no min.
battery charge condition, etc. This is probably not what you
want.
"new" models
The behaviour here is as expected - the power is cut off after
the EEPROM defined grace period. The UPS will wake up when the
power returns, after the EEPROM defined delay AND if the EEPROM
defined min. battery charge level is met. The delay is counted
from the power's return.
CS (aka "force OB hack")
This is a trick to make UPS power down even if it's running on
mains. Immediately before issuing S, "simulate power failure" is
issued. The remaining behaviour is as in S case.
The name came from APC CS models, where such trick was used to
power down UPSes in consistent fashion using only S. It's better to
use @nnn command if your UPS supports it (and is not too old, see
below).
@nnn (hard hibernate)
This is basic command used to hibernate UPS regardless if it's
running on batteries or on mains. The option takes 3 digits
argument which can be used to specify additional wakeup delay (in 6
minute units).
"old" models
The behaviour is - unfortunately - similary primitive to S. The
UPS unconditionally wakes up after nnn*6 minutes - it doesn't
care if the power returned ! If nnn = 000, then UPS will do
precisely nothing. On those models you're better specifying nnn
> 0, if you can estimate the kind of power problems that might
be happening in your environment. Another thing to consider
with "old" models - you might lose the connection with the UPS,
until it wakes up (with S, the serial connection is kept
alive).
"new" models
All the usual variables defined in EEPROM are respected (see
S). Additionally, if nnn > 0, the nnn*6 minutes are added to
EEPROM defined delay. UPS will not power up if it's running on
batteries, contrary to what "old" models used to do - the
combined delay is counted from the moment of power return.
Supposedly there exist models that take 2 digits instead of 3. Just
in case, NUT also supports such variation. You have to provide
exactly 2 digits to trigger it (awd option, or argument to one of
the supported instant commands).
K (delayed poweroff)
This is permanent poweroff - the UPS will not wake up
automatically. On newer units, it will respect applicable EEPROM
variables.
Z (instant poweroff)
This is also permanent poweroff - the UPS will not wake up
automatically. The poweroff is executed immediately.
SHUTDOWN CONTROL BY NUT
There are three options used to control the shutdown behaviour.
sdtype=[0-5]
This option takes a single digit (0-5) as an argument. See below
for details.
advorder=no|[0-4]+
This option takes string of digits as an argument. Methods listed
are tried in turn until one of them succeedes. Note that the
meaning of digits is different from sdtype. See below for details.
awd=[0-9]{1,3}
This option lets you specify additional wakeup delay used by @. If
you provide exactly 2 digits, the driver will try 2 digits
variation (see previous section for more info). Otherwise standard
3 digits variation is used. Note: the time unit is 6 minutes !
Keep in mind that sdtype and advorder are mutually exclusive. If
advorder is provided, sdtype is ignored. If advorder is set to 'no',
sdtype is used instead.
If nothing is provided, NUT will assume sdtype=0 - which is generally
fine for anything not too ancient or not too quirky.
SDTYPE
The values permitted are from 0 to 5. Only one can be specified.
Anything else will cause apcsmart to exit.
0
issue soft hibernate (S) if the UPS is running on batteries,
otherwise issue hard hibernate (@)
1
issue soft hibernate (S) (if on batteries), and if it fails (or on
mains) - try hard hibernate (@)
2
issue instant poweroff (Z)
3
issue delayed poweroff (K)
4
issue "force OB hack" (CS)
5
issue hard hibernate (@)
Note
Hard hibernate's additional wakeup delay can be provided by awd.
ADVORDER
The argument is either a word 'no', or a string of 1 - 5 digits in [0 -
4] range. Each digit maps to the one of shutdown methods supported by
APC UPSes. Methods listed in this way are tried in order, until one of
them succedes.
If advorder is undefined or set to 'no', sdtype is used instead.
The mapping is as follows:
0 soft hibernate (S)
1 hard hibernate (@)
2 delayed poweroff (K)
3 instant poweroff (Z)
4 "force OB hack" (CS)
Note
Hard hibernate's additional wakeup delay can be provided by awd.
IGNORING LB STATE
APC units - even if they report LB mode - will not go into shutdown
automatically. This gives us even more control with reference to "when
to actually shutdown PSU". Since version 2.6.2, NUT supports ignorelb
option in driver’s section of ups.conf(5). When such option is in
effect, the core driver will ignore LB state as reported by specific
driver and start shutdown basing the decision only on two conditions:
battery.charge < battery.charge.low
OR
battery.runtime < battery.runtime.low
Of course - if any of the variables are not available, the appropriate
condition is not checked. If you want to explicitly disable one of the
conditions, simply override the right hand variable causing the
condition to always evaluate to false (you can even provide negative
numbers).
APC UPSes don’t have battery.charge.low - you will have to define it if
you want to use such condition (prefix the variable with override. or
default.).
"New" units have battery.runtime.low, but depending on battery quality,
firmware version, calibration and UPS load - this variable can be
underestimated quite a bit - especially right after going into OB
state. This in turn can cause LB to be asserted, which under normal
conditions will cause NUT to initiate the shutdown. You might want to
disable this condition entirely, when relying on ignorelb option (this
was actually the main motivation behind introduction of such feature).
Simple example:
[apc]
ignorelb
override.battery.charge.low = 15
override.battery.runtime.low = -1
This would cause apcsmart to go into shutdown only if detected battery
charge < 15%. Runtime condition is always false in this example.
You could ask - why bother ? Well, the reason is already hinted above.
APC units can be very picky about the batteries, and their firmware can
underestimate the remaining runtime (especially right after going into
OB state). ignorelb option and override.* let you remain in control of
the UPS, not UPS in control of you.
Furthermore, this allows to specify conditions similary to how it’s
done in apcupsd daemon, so it should be welcome by people used to that
software.
SUPPORTED INSTANT COMMANDS
The apcsmart driver exposes following instant commands:
shutdown.return
executes soft hibernate
shutdown.return cs
executes "force OB hack"
shutdown.return at:<nbr>
executes "hard hibernate" with <nbr>*6 minutes additional wakeup
delay (<nbr> format is the same as of awd option)
shutdown.stayoff
executes "delayed poweroff"
load.off
executes "instant poweroff"
All the above commands must be issued 2nd time to have any effect (no
less than 3 seconds, and no more than 15 seconds after the initial
call). Those commands are mostly useful for manual testing, when your
machine is not powered by the UPS you're testing.
Other supported commands:
· load.on
· test.panel.start
· test.failure.start
· test.battery.start
· test.battery.stop
· bypass.start
· bypass.stop
· calibrate.start
· calibrate.stop
PREVIOUS DRIVER VERSION
Previous driver is still available as apcsmart-old, should there be any
need to use earlier version (bugs, incompatiblities with new
functionality, etc.). In due time, apcsmart-old will be phased out
completely, but this won’t happen until the new version gets solid
exposure with no pending issues.
BUGS
Some older APC UPS models return bogus data in the status register
during a front panel test. This is usually detected and discarded, but
some other unexpected values have occasionally slipped through.
APC UPS models with both USB and serial ports require a power cycle
when switching from USB communication to serial, and perhaps vice
versa.
AUTHOR
Nigel Metheringham <Nigel.Metheringham@Intechnology.co.uk> (drawing
heavily on the original apcsmart driver by Russell Kroll). This driver
was called newapc for a time and was renamed in the 1.5 series. In
2.6.2 it was renamed to apcsmart-old, being superseded by updated
version with new features, which is maintained by Michal Soltys
<soltys@ziu.info>
SEE ALSOnutupsdrv(8), ups.conf(5), usbhid-ups(8), solis(8)
Internet resources:
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
Network UPS Tools 2.7.3 04/17/2015 APCSMART(8)