MGEUPSD(8)	      Linux System Administrator's Manual	    MGEUPSD(8)

NAME
       mgeupsd -- monitor a state of MGE Pulsar UPS connected to RS-232 port.

SYNOPSIS
       /sbin/mgeupsd [options] serial-device

DESCRIPTION
       mgeupsd is a daemon process that sits in the background and check state
       of the UPS every 10 (by default) seconds. As  soon  as  mgeupsd	senses
       that the power is failing it notifies init(8) and init will execute the
       powerwait and powerfail entries. If mgeupsd senses that the  power  has
       been  restored,	it  notifies  init  again  and	init  will execute the
       powerokwait entries. If mgeupsd senses that the UPS batteries has  less
       than 20% of its energy it notifies init again and init will execute the
       powerfailnow entries.

OPTIONS
       -pwroff
	      turn ups off.

       -q     same as -pwroff.

       -l     use syslog for  reporting.  off  by  default,  but  very	useful
	      option.

       -i N   set UPS checking interval to N seconds. Default 10

       -li N  set  to  N interval for reporting battery low status. Usually if
	      battery low status reported init must start immediate  shutdown.
	      When  shutdown  started  it  must	 kill mgeupsd.	If mgeupsd not
	      killed during N seconds the low battery status will be  reported
	      again. Default 30

       -s on|off
	      turn power saving mode on or off (see UPS manual for more infor‐
	      mation about power saving mode)

       -p on|off
	      turn total discharge protection on or off (see  UPS  manual  for
	      more information about  total discharge protection)

       -t trace_file
	      turn  on	trace  of  UPS<->computer communication protocol.  Use
	      only  for	 debugging  -  this  produce  a	 huge  output.	 Since
	      trace_file stay opened all time to its remove you must kill mge‐
	      upsd before.

       serial-device
	      Some serial port that is connected to your MGE Pulsar device.

       Since version 0.3 you may use your UPS not only for protecting the com‐
       puter,  powered from UPS. You may connect to computer UPS which protect
       any other equipment (f.e. rack-mount modems). For this case  there  are
       some additional options:

       -pwrfile filename
	      Change  power status filename from default (/etc/powerstatus) to
	      something else.

       -process pid
	      Change pid of process to send SIGPWR from default (1 - init)  to
	      pid.  mgeupsd check is this process running.

       -run /path/cmd
	      Don't send SIGPWR at all, but run specified program & give power
	      status file as a first argument. Note that program must be spec‐
	      ified with full path.

       -swpwr W,B
	      Switch  (turn  off/on) power. Argument W set the time in minutes
	      to wait before turning power back to on. Argument B set the time
	      in  seconds  to  wait before turning power off. You may set only
	      one time (f.e. -swpwr W or -swpwr ,B or even -swpwr ,) - in this
	      case  unspecified	 time  will  be	 set  to 0. Note that the time
	      before power off must be in seconds, but the time	 before	 power
	      on  - in minutes. If waiting time for turn UPS back to on set to
	      0, power will be turned off just about 5 seconds.

DIAGNOSTICS
       Just because UPS communicate with macine through RS-232 interface  mge‐
       upsd  report  to	 syslog	 if  communication with UPS lost. Mgeupsd will
       notify you about this fact every minute. When it sees that the  connec‐
       tion has been restored it will say so.

BUGS
       Well, when you found bug in this program send me E-mail about this.

SEE ALSO
       shutdown(8), init(8), inittab(5).

AUTHOR
       Stanislav Voronyi, stas@esc.kharkov.com

				 Dec 23, 1998			    MGEUPSD(8)
[top]

List of man pages available for DragonFly

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net