UPSCMD(8)		    Network UPS Tools (NUT)		     UPSCMD(8)

NAME
       upscmd - UPS administration program for instant commands

SYNOPSIS
       upscmd -h

       upscmd -l ups

       upscmd [-u username] [-p password] ups command

DESCRIPTION
       upscmd  allows  you  to invoke "instant commands" in your UPS hardware.
       Not all hardware supports this, so check the list with  -l  to  see  if
       anything will work on your equipment.

       On  hardware  that  supports  it, you can use this program to start and
       stop battery tests, invoke a front panel test (beep!), turn the load on
       or off, and more.

OPTIONS
       -h     Display the help message.

       -l ups Show  the	 list of supported instant commands on that UPS.  Some
	      hardware may not support any of them.

       -u username
	      Set the username for the connection  to  the  server.   This  is
	      optional, and you will be prompted for this when invoking a com‐
	      mand if -u is not used.

       -p password
	      Set the password to authenticate to the server.	This  is  also
	      optional like -u, and you will be prompted for it if necessary.

       ups    Connect  to  this UPS.  The format is upsname[@hostname[:port]].
	      The default hostname is "localhost".

UNATTENDED MODE
       If you run this program inside a shell script or similar	 to  invoke  a
       command, you will need to specify all of the information on the command
       line.  This means using -u and -p.  Otherwise it will put up  a	prompt
       and your program will hang.

       This  is	 not  necessary	 when displaying the list, as the username and
       password are not required for read‐only mode.

DANGEROUS COMMANDS
       Some drivers like apcsmart(8) have built‐in paranoia for the  dangerous
       commands	 like  load.off.  To make them actually turn off the load, you
       will have to send the command twice within a short  window.   That  is,
       you  will  have	to  send  it  once, then send it again after 3 seconds
       elapse but before 15 seconds pass.

       This paranoia is entirely defined within the driver.  upsd  and	upscmd
       have no control over the timing.

DIAGNOSTICS
       upscmd won't work unless you provide a valid username and password.  If
       you get "access denied" errors, make sure that your  upsd.users(5)  has
       an  entry  for you, and that the username you are using has permissions
       to SET variables.

BUGS
       There is currently no way to tell the user  when	 the  driver  requires
       confirmation to invoke a command such as load.off.  Similarly, there is
       not yet a way to tell the user if a command succeeds or fails.

       This is on the list of things to fix in the future, so  don't  despair.
       It involves magic cookies.

SEE ALSO
       upsd(8), upsrw(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

				Mon Jan 22 2007			     UPSCMD(8)
[top]

List of man pages available for Mandriva

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net