[printable version]

UPSCODE2(8)		    Network UPS Tools (NUT)		   UPSCODE2(8)

NAME
       upscode2 - Driver for UPScode II compatible UPS equipment

NOTE
       This  man  page	only  documents	 the hardware‐specific features of the
       upscode2 driver.	 For information about the core	 driver,  see  nutups‐
       drv(8).

SUPPORTED HARDWARE
       This  driver  supports  UPS  equipment  which can be controlled via the
       UPScode II protocol.  This is mainly Fiskars, Powerware equipment,  but
       also some (probably OEM'ed) products from Compaq.

EXTRA ARGUMENTS
       This   driver   supports	  the	following  optional  settings  in  the
       ups.conf(5):

       manufacturer=value
	      Autodetection of this parameter is  not  possible	 yet  (and  it
	      probably	never  will  be).  Therefore  this user defined string
	      accepts any name. The default is unknown.

       input_timeout=value
	      The timeout waiting for a response from the UPS. Some UPS models
	      have  shown  to  be  rather slow, resulting in frequent messages
	      about empty responses  from  the	UPS.  If  you  see  this,  try
	      increasing this value.

       output_pace=value
	      Delay  between  characters  sent	to the UPS. This was added for
	      completeness with the above parameter. It has not	 shown	to  be
	      needed yet.

       baudrate=value
	      The  default  baudrate  is  1200,	 which is the standard for the
	      UPScode II protocol.

       full_update_timer=value
	      Number of seconds between collection of normative values.

       use_crlf
	      Flag to set if commands towards to UPS  need  to	be  terminated
	      with CR-LF, and not just CR.

       use_pre_lf
	      Flag  to	set  if	 commands towards to UPS need to be introduced
	      with an LF.  A Compaq T1500h is known to need this.

UPSCMD
       The driver supports the following commands for those UPSen that support
       them.   The  available commands are autodetected during initialization,
       so you should check availability with upscmd -l.

       test.panel.start ‐ Start UPS self test

       test.battery.start ‐ Start battery self test

       beeper.enable ‐ Enable UPS beeper

       beeper.disable ‐ Disable UPS beeper

       shutdown.return ‐ Shut down in 1 second and wait for power to return

       shutdown.stayoff ‐ Shut down in 1 seconds

       shutdown.reboot ‐ Shut down in 1 seconds and reboot after 1 minute

       shutdown.reboot.graceful ‐ Shut down in 20 seconds and reboot  after  1
       minute

NOTES
       The Powerware UPS models that this driver has been tested against until
       now has not returned a value for battery.charge. Therefore  the	driver
       will  guesstimate  a value based on the nominal battery min/max and the
       current battery voltage.

AUTHOR
       Håvard Lygre <hklygre@online.no>, Niels Baggesen <niels@baggesen.net>

SEE ALSO
   The core driver:
       nutupsdrv(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

				Tue Oct 19 2004			   UPSCODE2(8)
[top]

List of man pages available for Mandriva

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net