MEGATEC(8)		    Network UPS Tools (NUT)		    MEGATEC(8)

NAME
       megatec - Driver for Megatec protocol based UPS equipment

NOTE
       This  man  page	only  documents	 the hardware‐specific features of the
       megatec driver. For information about  the  core	 driver,  see  nutups‐
       drv(8).

SUPPORTED HARDWARE
       The  megatec  driver  is	 known to work with various UPSes from Blazer,
       Energy Sistem, Fenton Technologies, Mustek and  many  others.  The  NUT
       compatibility table lists all the known supported models. Keep in mind,
       however, that other models not listed there may also be	supported  but
       haven't been tested.

       On  models  with	 both a serial port (RS-232) and an USB port, only the
       serial port is supported. Connecting a computer which does not  have  a
       serial interface to the UPS serial port using a USB-to-serial converter
       should work, provided the converter is supported by your operating sys‐
       tem.

EXTRA ARGUMENTS
       This driver supports some extra parameters (see ups.conf(5)):

       mfr=string

	      Optional.	 Specify the UPS manufacturer name.

       model=string

	      Optional.	 Specify the UPS model name.

       serial=string

	      Optional.	 Specify the UPS serial number.

       offdelay=int

	      Optional.	 After receiving a shutdown command, the UPS will wait
	      this many minutes before turning off the load. Specify  this  if
	      the  UPS must remain online for a short period of time after the
	      computer has powered down. The default is 0  (turn  off  immedi‐
	      ately).

       ondelay=int

	      Optional.	  After	 turning  off the load (see offdelay), the UPS
	      will wait at least this many minutes before coming back  online.
	      If  line	power gets restored before this delay expires, the UPS
	      will wait until it does. If line power gets restored after  this
	      delay  expires, the UPS will power on the load immediately.  The
	      default is 2 minutes.

       lowbatt=float

	      Optional.	 Low battery level (%). Overrides the hardware default
	      level.  Cannot  be used if the driver is unable to calculate the
	      charge percentage for your UPS automatically  (see  KNOWN	 PROB‐
	      LEMS) and the battvolts parameter isn't specified.

       battvolts=float:float

	      Optional.	 The battery voltage interval (see KNOWN PROBLEMS).

       battvoltmult=num

	      Optional.	 Multiply the reported battery voltage by this number.
	      Some devices report only a fraction of the total	battery	 volt‐
	      age. The default is 1.

       dtr=int

	      Optional.	  Some	UPS  models  need the DTR serial line set to a
	      specific state, either 0 or 1. See also rts.

       rts=int

	      Optional.	 Some UPS models need the RTS serial  line  set	 to  a
	      specific state, either 0 or 1. See also dtr.

       ignoreoff

	      Optional.	  This	option should be used if upsc(8) shows the UPS
	      status as OFF when it's clearly on. This will force  the	driver
	      to ignore the OFF status altogether.

       sendpace=int

	      Optional.	  This	option can be used to change the wait interval
	      between each character that is sent to the UPS,  between	1  and
	      1000  milliseconds.  Some	 models	 may  need this if the default
	      interval (100 milliseconds) proves to be too long, or too short.

UPS COMMANDS
       This driver supports some instant commands (see upscmd(8)):

       beeper.toggle
	      Toggle the UPS beeper. (Not available on some hardware.)

       load.on
	      Turn on the load immediately.

       load.off
	      Turn off the load immediately (see KNOWN PROBLEMS).

       reset.input.minmax
	      Reset minimum and maximum input voltage status.

       reset.watchdog
	      Restarts the UPS watchdog timeout. The watchdog is started if it
	      isn't  running,  which means the UPS shuts down one minute after
	      this command is executed	for  the  last	time,  restarting  one
	      minute  afterwards.  To  cancel  the  watchdog,  run  the "shut‐
	      down.stop" command.

       shutdown.return
	      Turn off the load and return when power is back. Uses the timers
	      defined by ondelay and offdelay.

       shutdown.stayoff
	      Turn  off the load and remain off (see KNOWN PROBLEMS). Uses the
	      timer defined by offdelay.

       shutdown.stop
	      Stop a shutdown in progress.

       test.battery.start.deep
	      Perform a long battery test (Not available on some hardware.)

       test.battery.start
	      Perform a (10 second) battery test.

       test.battery.stop
	      Stop a running battery test. (Not available on some hardware.)

KNOWN PROBLEMS
       The battery charge (%) value is only a best-effort calculation and  may
       be  incorrect,  or  non-existant, for some UPS models. In any case, you
       can always resort to finding the voltages at which the battery  becomes
       fully discharged and fully charged, and specify them manually using the
       "battvolts" option.  If you do this, please notify the author  of  this
       driver so that information can be added to the NUT hardware compatibil‐
       ity list. Note that if you also specified  the  "battvoltmult"  option,
       you  need  to  divide the found voltages for fully discharged and fully
       charged by this number.

       Some UPS commands aren't supported by all models. In  most  cases,  the
       driver  will  send  a  message to the system log when the user tries to
       execute an unsupported command. Unfortunately, some models  don't  even
       provide a way for the driver to check for this, so the unsupported com‐
       mands will silently fail.

       Both the "load.off" and "shutdown.stayoff" instant commands  are	 meant
       to turn the load off indefinitely. However, some UPS models don't allow
       this.  When this is the case, the driver will tell the UPS to turn  off
       the  load for 9999 minutes (about 7 days) and a message will be sent to
       the system log.

       Some models report a bogus value for the beeper status (will always  be
       "enabled" or "disabled"). So, the "beeper.toggle" command may appear to
       have no effect in the status reported by the driver when, in  fact,  it
       is working fine.

       The temperature value is also known to be bogus in some models.

AUTHOR
       Carlos Rodrigues <carlos.efr at mail.telepac.pt>

SEE ALSO
       nutupsdrv(8), upsc(8), upscmd(8), upsrw(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

				Sat Jan 14 2006			    MEGATEC(8)
[top]

List of man pages available for Mandriva

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net