netxml-ups man page on Mandriva

Man page or keyword search:  
man Server   17060 pages
apropos Keyword Search (all sections)
Output format
Mandriva logo
[printable version]

netxml-ups(8)		    Network UPS Tools (NUT)		 netxml-ups(8)

NAME
       netxml‐ups  -  Driver  for  Eaton  /MGE Network Management Card / Proxy
       (XML/HTTP Protocol) equipment

NOTE
       This man page only documents  the  hardware‐specific  features  of  the
       netxml‐ups  driver.  For information about the core driver, see nutups‐
       drv(8).

SUPPORTED HARDWARE
       netxml‐ups support all recent Eaton / MGE models which  use  a  Network
       Management Card or Proxy (MGE XML/HTTP protocol based). This applies to
       both Eaton (previously MGE Office Protection Systems) and  to  MGE  UPS
       SYSTEMS.	 Supported card and proxy models are:

	   NMC Minislot (Ref 66102, firmware EA or newer),
	   SNMP/Web Minislot card (Ref 66244)
	   NMC Transverse (Ref 66074),
	   NMC & Modbus/JBus (Ref 66103),
	   Network Management Proxy,
	   ePDU Monitored (newer version).

       Older models, such as SNMP card (Ref 66062 and Ref 66045), use the SNMP
       protocol and should use the snmp‐ups driver with the "mibs=mge" parame‐
       ter.

EXTRA ARGUMENTS
       This   driver   supports	  the	following  optional  settings  in  the
       ups.conf(5):

       timeout=value
	      The timeout for connecting to and reading from the UPS. Defaults
	      to  5  seconds.  Don't change this value unless you know exactly
	      what you're doing.

	      This value must never be higher than half the MAXAGE value spec‐
	      ified  in upsd.conf(5), otherwise you risk that upsd(8) declares
	      the driver stale while it is waiting for a connection  to	 time‐
	      out.

       login=value
	      Set  the	login  value for authenticated mode. This feature also
	      needs the password argument, and allows value  settings  in  the
	      card.  This feature is not used yet.

       password=value
	      Set  the password value, needed with the login for authenticated
	      mode.  This feature is not used yet.

IMPLEMENTATION
       The hostname of the UPS is specified with the "port" value in ups.conf,
       i.e.:

	    [mgexml]
		 driver = netxml-ups
		 port = http://netxml-ups.example.com:80

       Specifying the method how to connect to the UPS (http, https) is manda‐
       tory.  If the port is equal to the default for the method specified (80
       for http, 443 for https) it may be omitted.

       In  order not to overload older NMCs by polling them too frequently, it
       is recommended to increase the "pollinterval"  (see  nutupsdrv(8))  and
       ups.conf(5)) to at least 5 seconds.

KNOWN ISSUES
       Don't  connect to the UPS through a proxy. Although it would be trivial
       to add support for proxies, this is not recommended and don't  ask  for
       it.  Not	 only  because it will prevent the driver to make a persistent
       connection to the UPS, but also it adds an additional failure mode.  If
       the proxy goes down (for whatever reason), the driver will no longer be
       able to reach the UPS.

AUTHORS
       Arjen de Korte <adkorte-guest@alioth.debian.org>

SEE ALSO
   The core driver:
       nutupsdrv(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

				Mon Aug 10 2009			 netxml-ups(8)
[top]

List of man pages available for Mandriva

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net