UPSMON.CONF(5)		    Network UPS Tools (NUT)		UPSMON.CONF(5)

NAME
       upsmon.conf - Configuration for Network UPS Tools upsmon

DESCRIPTION
       This  file's  primary  job is to define the systems that upsmon(8) will
       monitor and to tell it how to shut down the system when necessary.   It
       will  contain  passwords,  so  keep it secure.  Ideally,only the upsmon
       process should be able to read it.

       Additionally, other optional configuration values can be	 set  in  this
       file.

CONFIGURATION DIRECTIVES
       DEADTIME seconds

	      upsmon  allows  a UPS to go missing for this many seconds before
	      declaring it "dead".  The default is 15 seconds.

	      upsmon requires a UPS to provide status  information  every  few
	      seconds (see POLLFREQ and POLLFREQALERT) to keep things updated.
	      If the status fetch fails, the UPS is marked stale.  If it stays
	      stale for more than DEADTIME seconds, the UPS is marked dead.

	      A	 dead  UPS  that was last known to be on battery is assumed to
	      have changed to a low battery condition.	This may force a shut‐
	      down  if it is providing a critical amount of power to your sys‐
	      tem.  This seems disruptive, but the  alternative	 is  barreling
	      ahead into oblivion and crashing when you run out of power.

	      Note:  DEADTIME  should  be  a multiple of POLLFREQ and POLLFRE‐
	      QALERT.  Otherwise,  you'll have	"dead"	UPSes  simply  because
	      upsmon  isn't  polling them quickly enough.  Rule of thumb: take
	      the larger of the two POLLFREQ values, and multiply by 3.

       FINALDELAY seconds

	      When running in master mode, upsmon waits this long after	 send‐
	      ing  the	NOTIFY_SHUTDOWN	 to  warn  the users.  After the timer
	      elapses, it then runs your SHUTDOWNCMD.  By default this is  set
	      to 5 seconds.

	      If  you  need  to	 let  your users do something in between those
	      events, increase this number.  Remember, at this point your  UPS
	      battery is almost depleted, so don't make this too big.

	      Alternatively,  you  can	set  this  very	 low so you don't wait
	      around when it's time to shut down.  Some UPSes don't give  much
	      warning for low battery and will require a value of 0 here for a
	      safe shutdown.

	      Note: If FINALDELAY on the slave is greater than HOSTSYNC on the
	      master, the master will give up waiting for the slave to discon‐
	      nect.

       HOSTSYNC seconds

	      upsmon will wait up to this many seconds in master mode for  the
	      slaves  to  disconnect during a shutdown situation.  By default,
	      this is 15 seconds.

	      When a UPS goes critical (on battery + low battery, or  "FSD"  ‐
	      forced shutdown), the slaves are supposed to disconnect and shut
	      down right away.	The HOSTSYNC timer  keeps  the	master	upsmon
	      from sitting there forever if one of the slaves gets stuck.

	      This value is also used to keep slave systems from getting stuck
	      if the master fails to respond in time.	After  a  UPS  becomes
	      critical,	 the  slave  will  wait up to HOSTSYNC seconds for the
	      master to set the FSD flag.  If that timer  expires,  the	 slave
	      will assume that the master is broken and will shut down anyway.

	      This  keeps  the	slaves from shutting down during a short‐lived
	      status change to "OB LB" that the	 slaves	 see  but  the	master
	      misses.

       MINSUPPLIES num

	      Set the number of power supplies that must be receiving power to
	      keep this system running.	 Normal computers have just one	 power
	      supply, so the default value of 1 is acceptable.

	      Large/expensive  server  type systems usually have more, and can
	      run with a few missing.  The HP NetServer LH4 can run with 2 out
	      of  4,  for  example, so you'd set it to 2.  The idea is to keep
	      the box running as long as possible, right?

	      Obviously you have to put the redundant  supplies	 on  different
	      UPS circuits for this to make sense!  See big‐servers.txt in the
	      docs subdirectory for more information and ideas on how  to  use
	      this feature.

	      Also see the section on "power values" in upsmon(8).

       MONITOR system powervalue username password type

	      Each UPS that you need to be monitor should have a MONITOR line.
	      Not all of these need supply power to the system that is running
	      upsmon.  You may monitor other systems if you want to be able to
	      send notifications about status changes on them.

	      You must have at least one MONITOR directive in this file.

	      system is a UPS identifier.  It is in this form:

		   <upsname>[@<hostname>[:<port>]]

	      The default hostname is "localhost".  Some examples:

	       ‐ "su700@mybox" means a UPS called "su700" on a	system	called
	      "mybox".	This is the normal form.

	       ‐  "fenton@bigbox:5678"	is  a  UPS called "fenton" on a system
	      called "bigbox" which runs upsd(8) on port "5678".

	      powervalue is an integer representing the number of  power  sup‐
	      plies  that the UPS feeds on this system.	 Most normal computers
	      have one power supply, and the UPS feeds it, so this value  will
	      be  1.  You need a very large or special system to have anything
	      higher here.

	      You can set the powervalue to 0 if you want  to  monitor	a  UPS
	      that doesn't actually supply power to this system.  This is use‐
	      ful when you want to have upsmon do notifications	 about	status
	      changes on a UPS without shutting down when it goes critical.

	      The  username  and  password on this line must match an entry in
	      that system's upsd.users(5).  If your  username  is  "monmaster"
	      and  your	 password  is "blah", the MONITOR line might look like
	      this:

	      MONITOR myups@bigserver 1 monmaster blah master

	      Meanwhile, the upsd.users on 'bigserver' would look like this:

		   [monmaster]

			password  = blah

			upsmon master	(or slave)

	      The type refers to the relationship with	upsd(8).   It  can  be
	      either  "master" or "slave".  See upsmon(8) for more information
	      on the meaning of these modes.  The mode you pick here also goes
	      in the upsd.users file, as seen in the example above.

       NOCOMMWARNTIME seconds

	      upsmon  will  trigger a NOTIFY_NOCOMM after this many seconds if
	      it can't reach any of the	 UPS  entries  in  this	 configuration
	      file.   It  keeps	 warning you until the situation is fixed.  By
	      default this is 300 seconds.

       NOTIFYCMD command

	      upsmon calls this to send messages when things happen.

	      This command is called with the full text of the message as  one
	      argument.	  The  environment  string NOTIFYTYPE will contain the
	      type string of whatever caused this event to happen.

	      If you need to use upssched(8), then you must make it your NOTI‐
	      FYCMD by listing it here.

	      Note  that  this is only called for NOTIFY events that have EXEC
	      set with NOTIFYFLAG.  See NOTIFYFLAG below for more details.

	      Making this some sort of shell script might not be a  bad	 idea.
	      For more information and ideas, see pager.txt in the docs direc‐
	      tory.

	      Remember, this also needs to be one element in the configuration
	      file, so if your command has spaces, then wrap it in quotes.

		   NOTIFYCMD "/path/to/script --foo --bar"

	      This  script  is	run  in the background ‐ that is, upsmon forks
	      before it calls out to start it.	This means that your NOTIFYCMD
	      may  have	 multiple instances running simultaneously if a lot of
	      stuff happens all at once.  Keep this  in	 mind  when  designing
	      complicated notifiers.

       NOTIFYMSG type message

	      upsmon  comes  with  a set of stock messages for various events.
	      You can change them if you like.

		   NOTIFYMSG ONLINE "UPS %s is getting line power"

		   NOTIFYMSG ONBATT "Someone pulled the plug on %s"

	      Note that %s is replaced with the identifier of the UPS in ques‐
	      tion.

	      Possible values for type:

		   ONLINE ‐ UPS is back online

		   ONBATT ‐ UPS is on battery

		   LOWBATT ‐ UPS is on battery and has a low battery (is crit‐
	      ical)

		   FSD ‐ UPS is being shutdown by the master  (FSD  =  "Forced
	      Shutdown")

		   COMMOK ‐ Communications established with the UPS

		   COMMBAD ‐ Communications lost to the UPS

		   SHUTDOWN ‐ The system is being shutdown

		   REPLBATT ‐ The UPS battery is bad and needs to be replaced

		   NOCOMM ‐ A UPS is unavailable (can't be contacted for moni‐
	      toring)

	      The message must be one element in the configuration file, so if
	      it contains spaces, you must wrap it in quotes.

		   NOTIFYMSG NOCOMM "Someone stole UPS %s"

       NOTIFYFLAG type flag[+flag][+flag]...

	      By  default, upsmon sends walls global messages to all logged in
	      users) via /bin/wall and writes to the syslog when  things  hap‐
	      pen.  You can change this.

	      Examples:

		   NOTIFYFLAG ONLINE SYSLOG

		   NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC

	      Possible values for the flags:

		   SYSLOG ‐ Write the message to the syslog

		   WALL ‐ Write the message to all users with /bin/wall

		   EXEC ‐ Execute NOTIFYCMD (see above) with the message

		   IGNORE ‐ Don't do anything

	      If you use IGNORE, don't use any other flags on the same line.

       POLLFREQ seconds

	      Normally	upsmon	polls  the upsd(8) server every 5 seconds.  If
	      this is flooding your network with activity,  you	 can  make  it
	      higher.	You  can  also	make it lower to get faster updates in
	      some cases.

	      There are some catches.  First, if  you  set  the	 POLLFREQ  too
	      high,  you may miss short‐lived power events entirely.  You also
	      risk triggering the DEADTIME (see above) if you use a very large
	      number.

	      Second,  there  is  a point of diminishing returns if you set it
	      too low.	While upsd normally has all of the data	 available  to
	      it  instantly,  most  drivers  only  refresh the UPS status once
	      every 2 seconds.	Polling any more than that usually doesn't get
	      you the information any faster.

       POLLFREQALERT seconds

	      This  is	the interval that upsmon waits between polls if any of
	      its UPSes are on battery.	 You can use this along with  POLLFREQ
	      above to slow down polls during normal behavior, but get quicker
	      updates when something bad happens.

	      This should always be equal to or lower than the POLLFREQ value.
	      By default it is also set 5 seconds.

	      The  warnings from the POLLFREQ entry about too‐high and too‐low
	      values also apply here.

       POWERDOWNFLAG filename

	      upsmon creates this file when running in master  mode  when  the
	      UPS  needs to be powered off.  You should check for this file in
	      your shutdown scripts and call upsdrvctl shutdown if it exists.

	      This is done to forcibly reset the slaves,  so  they  don't  get
	      stuck at the "halted" stage even if the power returns during the
	      shutdown process.	 This usually does not work well  on  contact‐
	      closure UPSes that use the genericups driver.

	      See  the	shutdown.txt  file  in	the docs subdirectory for more
	      information.

       RBWARNTIME seconds

	      When a UPS says that it needs  to	 have  its  battery  replaced,
	      upsmon  will  generate a NOTIFY_REPLBATT event.  By default this
	      happens every 43200 seconds ‐ 12 hours.

	      If you need another value, set it here.

       RUN_AS_USER username

	      upsmon normally runs the bulk of	the  monitoring	 duties	 under
	      another user ID after dropping root privileges.  On most systems
	      this means it runs as "nobody", since that's  the	 default  from
	      compile‐time.

	      The catch is that "nobody" can't read your upsmon.conf, since by
	      default it is installed so that only root	 can  open  it.	  This
	      means  you won't be able to reload the configuration file, since
	      it will be unavailable.

	      The solution is to create a new user just for upsmon, then  make
	      it  run  as that user.  I suggest "nutmon", but you can use any‐
	      thing that isn't already taken on your system.   Just  create  a
	      regular  user with no special privileges and an impossible pass‐
	      word.

	      Then, tell upsmon to run as  that	 user,	and  make  upsmon.conf
	      readable	by  it.	  Your reloads will work, and your config file
	      will stay secure.

	      This file should not be writable by the upsmon user, as it would
	      be  possible  to exploit a hole, change the SHUTDOWNCMD to some‐
	      thing malicious, then wait for upsmon to be restarted.

       SHUTDOWNCMD command

	      upsmon runs this command when the system	needs  to  be  brought
	      down.   If  it  is a slave, it will do that immediately whenever
	      the current overall power	 value	drops  below  the  MINSUPPLIES
	      value above.

	      When  upsmon  is	a  master, it will allow any slaves to log out
	      before starting the local shutdown procedure.

	      Note that the command needs to be	 one  element  in  the	config
	      file.   If your shutdown command includes spaces, then put it in
	      quotes to keep it together, i.e.:

		   SHUTDOWNCMD "/sbin/shutdown -h +0"

SEE ALSO
       upsmon(8), upsd(8), nutupsdrv(8).

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

				Mon Jan 22 2007			UPSMON.CONF(5)
[top]

List of man pages available for Mandriva

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net