upsmon man page on Mandriva

Man page or keyword search:  
man Server   17060 pages
apropos Keyword Search (all sections)
Output format
Mandriva logo
[printable version]

UPSMON(8)		    Network UPS Tools (NUT)		     UPSMON(8)

NAME
       upsmon - UPS monitor and shutdown controller

SYNOPSIS
       upsmon -h

       upsmon -c command

       upsmon [-D] [-p] [-u user]

DESCRIPTION
       upsmon is the client process that is responsible for the most important
       part of UPS monitoring ‐ shutting down the system when the  power  goes
       out.   It  can  call out to other helper programs for notification pur‐
       poses during power events.

       upsmon can monitor multiple systems using a single process.  Every  UPS
       that  is defined in the upsmon.conf(5) configuration file is assigned a
       power value and a type (slave or master).

OPTIONS
       -h     Display the help message.

       -c command
	      Send the command command to the existing upsmon process.	 Valid
	      commands are:

	      fsd ‐ shutdown all master UPSes (use with caution)

	      stop ‐ stop monitoring and exit

	      reload ‐ reread upsmon.conf(5) configuration file.  See "reload‐
	      ing nuances" below if this doesn't work.

       -D     Raise the debugging level.  upsmon will run  in  the  foreground
	      and  prints  information on stdout about the monitoring process.
	      Use this multiple times for more details.

       -K     Test for the shutdown flag.  If it exists and contains the magic
	      string  from  upsmon,  then  upsmon will exit with EXIT_SUCCESS.
	      Any other condition will make upsmon exit with EXIT_FAILURE.

	      You can test for a successful exit from upsmon -K in your	 shut‐
	      down  scripts to know when to call upsdrvctl(8) to shut down the
	      UPS.

       -p     Run privileged all the time.  Normally upsmon  will  split  into
	      two processes.  The majority of the code runs as an unprivileged
	      user, and only a tiny stub runs as root.	This switch will  dis‐
	      able that mode, and run the old "all root all the time" system.

	      This  is	not  the recommended mode, and you should not use this
	      unless you have a very good reason.

       -u user
	      Set the user for the unprivileged monitoring process.  This  has
	      no effect when using -p.

	      The  default  user  is  set  at  configure  time with 'configure
	      --with-user=...'.	 Typically this is 'nobody', but other distri‐
	      butions  will probably have a specific 'nut' user for this task.
	      If your notification scripts need to run as a specific user, set
	      it here.

	      You  can	also  set  this	 in  the  upsmon.conf(5) file with the
	      RUN_AS_USER directive.

UPS DEFINITIONS
       In the upsmon.conf(5), you must specify at least one UPS that  will  be
       monitored.  Use the MONITOR directive.

	    MONITOR system powervalue username password type

       The  system  refers  to	a  upsd(8)  server, in the form upsname[@host‐
       name[:port]].  The default hostname is "localhost".  Some examples fol‐
       low:

	‐ "su700@mybox" means a UPS called "su700" on a system called "mybox".
       This is the normal form.

	‐ "fenton@bigbox:5678" is a UPS called "fenton"	 on  a	system	called
       "bigbox" which runs upsd(8) on port "5678".

       The  powervalue	refers	to  how many power supplies on this system are
       being driven this UPS.  This is typically set to 1, but see the section
       on power values below.

       The  username  is a section in your upsd.users(5) file.	Whatever pass‐
       word you set in that section must match the password set in this file.

       The type set in that section must also match the type here ‐ master  or
       slave.	In general, a master process is one running on the system with
       the UPS actually plugged into a serial port, and	 a  slave  is  drawing
       power  from  the UPS but can't talk to it directly.  See the section on
       UPS types for more.

NOTIFY EVENTS
       upsmon senses several events as it monitors each UPS.  They are	called
       notify  events  as  they can be used to tell the users and admins about
       the change in status.  See the additional NOTIFY‐related sections below
       for information on customizing the delivery of these messages.

       ONLINE The UPS is back on line.

       ONBATT The UPS is on battery.

       LOWBATT
	      The UPS battery is low (as determined by the driver).

       FSD    The UPS has been commanded into the "forced shutdown" mode.

       COMMOK Communication with the UPS has been established.

       COMMBAD
	      Communication with the UPS was just lost.

       SHUTDOWN
	      The local system is being shut down.

       REPLBATT
	      The UPS needs to have its battery replaced.

       NOCOMM The UPS can't be contacted for monitoring.

NOTIFY COMMAND
       In  upsmon.conf(5),  you	 can  configure a program called the NOTIFYCMD
       that will handle events that occur.

	    NOTIFYCMD "path to program"

	    NOTIFYCMD "/usr/local/bin/notifyme"

       Remember to wrap the path in "quotes" if it contains any spaces.

       The program you run as your NOTIFYCMD can use the environment variables
       NOTIFYTYPE  and UPSNAME to know what has happened and on which UPS.  It
       also receives the notification message (see below) as  the  first  (and
       only) argument, so you can deliver a preformatted message too.

       Note  that the NOTIFYCMD will only be called for a given event when you
       set the EXEC flag by using the notify flags, below:

NOTIFY FLAGS
       By default, all notify events (see above)  generate  a  global  message
       (wall)  to  all	users,	plus  they are logged via the syslog.  You can
       change this with the NOTIFYFLAG directive in the configuration file:

	    NOTIFYFLAG notifytype flags

	    Examples:

	    NOTIFYFLAG ONLINE SYSLOG

	    NOTIFYFLAG ONBATT SYSLOG+WALL

	    NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC

       The flags that can be set on a given notify event are:

       SYSLOG Write this message to the syslog.

       WALL   Send this message to all users on the system via 'wall'.

       EXEC   Execute the NOTIFYCMD.

       IGNORE Don't do anything.  If you use this, don't use any of the	 other
	      flags.

       You can mix these flags.	 "SYSLOG+WALL+EXEC" does all three for a given
       event.

NOTIFY MESSAGES
       upsmon comes with default messages  for	each  of  the  NOTIFY  events.
       These can be changed with the NOTIFYMSG directive.

	    NOTIFYMSG type "message"

	    Examples:

	    NOTIFYMSG ONLINE "UPS %s is getting line power"

	    NOTIFYMSG ONBATT "Someone pulled the plug on %s"

       The  first  instance  of	 %s is replaced with the identifier of the UPS
       that generated the event.  These messages are used when	sending	 walls
       to  the	users directly from upsmon, and are also passed to the NOTIFY‐
       CMD.

POWER VALUES
       The "current overall power value" is the sum of all UPSes that are cur‐
       rently able to supply power to the system hosting upsmon.  Any UPS that
       is either on line or just on battery contributes to this number.	 If  a
       UPS  is	critical  (on  battery	and  low battery) or has been put into
       "forced shutdown" mode, it no longer contributes.

       A "power value" on a MONITOR line in the config file is the  number  of
       power supplies that the UPS runs on the current system.

	    MONITOR upsname powervalue username password type

       Normally, you only have one power supply, so it will be set to 1.

	    MONITOR myups@myhost 1 username mypassword master

       On  a large server with redundant power supplies, the power value for a
       UPS may be greater than 1.  You may also have more  than	 one  of  them
       defined.

	    MONITOR ups-alpha@myhost 2 username mypassword master

	    MONITOR ups-beta@myhost 2 username mypassword master

       You  can	 also set the power value for a UPS to 0 if it does not supply
       any power to that system.  This is generally used when you want to  use
       the  upsmon  notification features for a UPS even though it's not actu‐
       ally running the system that hosts upsmon.  Don't set this to  "master"
       unless  you  really  want  to  power this UPS off when this instance of
       upsmon needs to shut down for its own reasons.

	    MONITOR faraway@anotherbox 0 username mypassword slave

       The "minimum power value" is the number of power supplies that must  be
       receiving power in order to keep the computer running.

	    MINSUPPLIES value

       Typical PCs only have 1, so most users will leave this at the default.

	    MINSUPPLIES 1

       If  you have a server or similar system with redundant power, then this
       value will usually be set higher.  One that requires three  power  sup‐
       plies to be running at all times would simply set it to 3.

	    MINSUPPLIES 3

       When  the  current  overall  power  value drops below the minimum power
       value, upsmon starts the shutdown sequence.  This design allows you  to
       lose some of your power supplies in a redundant power environment with‐
       out bringing down the entire system while still	working	 properly  for
       smaller systems.

UPS TYPES
       upsmon  and upsd(8) don't always run on the same system.	 When they do,
       any UPSes that are directly attached to the upsmon host should be moni‐
       tored  in  "master" mode.  This makes upsmon take charge of that equip‐
       ment, and it will wait for slaves to disconnect	before	shutting  down
       the local system.  This allows the distant systems (monitoring over the
       network) to shut down cleanly before upsdrvctl shutdown runs and	 turns
       them all off.

       When  upsmon  runs  as  a slave, it is relying on the distant system to
       tell it about the state of the UPS.  When that UPS  goes	 critical  (on
       battery	and  low  battery),  it immediately invokes the local shutdown
       command.	 This needs to happen quickly.	Once it disconnects  from  the
       distant	upsd(8)	 server, the master upsmon will start its own shutdown
       process.	 Your slaves must all shut down before the  master  turns  off
       the power or filesystem damage may result.

       upsmon  deals  with  slaves that get wedged, hang, or otherwise fail to
       disconnect from upsd(8) in a timely manner  with	 the  HOSTSYNC	timer.
       During  a shutdown situation, the master upsmon will give up after this
       interval and it will shut down anyway.  This keeps the master from sit‐
       ting  there  forever (which would endanger that host) if a slave should
       break somehow.  This defaults to 15 seconds.

       If your master system is shutting down too quickly, set the  FINALDELAY
       interval	 to  something greater than the default 15 seconds.  Don't set
       this too high, or your UPS battery may run out of power before the mas‐
       ter upsmon process shuts down that system.

TIMED SHUTDOWNS
       For those rare situations where the shutdown process can't be completed
       between the time that low battery is signalled  and  the	 UPS  actually
       powers  off  the load, use the upssched(8) helper program.  You can use
       it along with upsmon to schedule a shutdown based on the	 "on  battery"
       event.	upssched can then come back to upsmon to initiate the shutdown
       once it's run on battery too long.

       This can be complicated and messy, so stick to the default critical UPS
       handling if you can.

REDUNDANT POWER SUPPLIES
       If  you	have  more  than one power supply for redundant power, you may
       also have more than one UPS feeding your computer.  upsmon  can	handle
       this.   Be  sure to set the UPS power values appropriately and the MIN‐
       SUPPLIES value high enough so that it keeps  running  until  it	really
       does need to shut down.

       For  example,  the  HP  NetServer  LH4  by default has 3 power supplies
       installed, with one bay empty.  It has two power cords, one per side of
       the  box.  This means that one power cord powers two power supply bays,
       and that you can only have two UPSes supplying power.

       Connect UPS "alpha" to the cord feeding two  power  supplies,  and  UPS
       "beta"  to  the	cord  that feeds the third and the empty slot.	Define
       alpha as a powervalue of 2, and beta as a powervalue  of	 1.   Set  the
       MINSUPPLIES to 2.

       When  alpha goes on battery, your current overall power value will stay
       at 3, as it's still supplying power.  However, once  it	goes  critical
       (on  battery and low battery), it will stop contributing to the current
       overall power value.  That means the value  will	 be  1	(beta  alone),
       which  is  less	than  2.   That is insufficient to run the system, and
       upsmon will invoke the shutdown sequence.

       However, if beta goes critical, subtracting its contribution will  take
       the  current  overall  value  from 3 to 2.  This is just high enough to
       satisfy the minimum, so the system will continue running as before.  If
       beta  returns  later, it will be re‐added and the current value will go
       back to 3.  This allows you to swap out UPSes, change a power  configu‐
       ration, or whatever, as long as you maintain the minimum power value at
       all times.

MIXED OPERATIONS
       Besides being able to monitor multiple UPSes, upsmon can	 also  monitor
       them as different roles.	 If you have a system with multiple power sup‐
       plies serviced by separate UPS batteries, it's possible to be a	master
       on one and a slave on the other.	 This usually happens when you run out
       of serial ports and need to do the monitoring  through  another	system
       nearby.

       This is also complicated, especially when it comes time to power down a
       UPS that has gone critical but doesn't supply the  local	 system.   You
       can  do	this  with some scripting magic in your notify command script,
       but it's beyond the scope of this manual.

FORCED SHUTDOWNS
       When upsmon is forced to bring down the local system, it sets the "FSD"
       (forced	shutdown) flag on any UPSes that it is running in master mode.
       This is used to synchronize slaves in the event that a master UPS  that
       is  otherwise OK needs to be brought down due to some pressing event on
       the master.

       You can manually invoke this mode on  the  master  upsmon  by  starting
       another copy with '-c fsd'.  This is useful when you want to initiate a
       shutdown before the critical stage through some external means, such as
       upssched(8).

DEAD UPSES
       In  the	event  that  upsmon  can't reach upsd(8), it declares that UPS
       "dead"  after   some   interval	 controlled   by   DEADTIME   in   the
       upsmon.conf(5).	If this happens while that UPS was last known to be on
       battery, it is assumed to have gone critical and no longer  contributes
       to the overall power value.

       upsmon  will  alert you to a UPS that can't be contacted for monitoring
       with a "NOCOMM" notifier by default every 300  seconds.	 This  can  be
       changed with the NOCOMMWARNTIME setting.

RELOADING NUANCES
       upsmon  usually	gives up root powers for the process that does most of
       the work, including handling signals like SIGHUP to reload the configu‐
       ration  file.   This means your upsmon.conf(8) file must be readable by
       the non‐root account that upsmon switches to.

       If you want reloads to work, upsmon must run as some user that has per‐
       missions to read the configuration file.	 I recommend making a new user
       just for this purpose, as making the file  readable  by	"nobody"  (the
       default user) would be a bad idea.

       See the RUN_AS_USER section in upsmon.conf(8) for more on this topic.

       Additionally, you can't change the SHUTDOWNCMD or POWERDOWNFLAG defini‐
       tions with a reload due to the  split‐process  model.   If  you	change
       those  values,  you must stop upsmon and start it back up.  upsmon will
       warn you in the syslog if you make changes to either  of	 those	values
       during a reload.

SIMULATING POWER FAILURES
       To  test	 a  synchronized  shutdown  without  pulling  the plug on your
       UPS(es), you need only set the forced shutdown (FSD) flag on them.  You
       can do this by calling upsmon again to set the flag ‐ i.e.:

	    upsmon -c fsd

       After  that,  the  master  and  the slaves will do their usual shutdown
       sequence as if the battery had gone critical.  This is much  easier  on
       your  UPS  equipment,  and  it  beats crawling under a desk to find the
       plug.

FILES
       upsmon.conf(5)

SEE ALSO
   Server:
       upsd(8)

   Clients:
       upsc(8), upscmd(8), upsrw(8), upsmon(8)

   CGI programs:
       upsset.cgi(8), upsstats.cgi(8), upsimage.cgi(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

				Mon Jan 22 2007			     UPSMON(8)
[top]

List of man pages available for Mandriva

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net