upsset.cgi(8)		    Network UPS Tools (NUT)		 upsset.cgi(8)

NAME
       upsset.cgi - Web‐based UPS administration program

SYNOPSIS
       upsset.cgi

NOTE
       As  a  CGI program, this should be invoked through your web server.  If
       you run it from the command line, it will sit there until you  give  it
       input resembling a POST request.

DESCRIPTION
       upsset.cgi lets you access many administrative functions within the UPS
       software from your web browser.	You can	 change	 settings  and	invoke
       instant commands where available.

CHANGING SETTINGS
       Some  UPS hardware allows you to change certain variables to other val‐
       ues.  To see what's available, pick a UPS from the chooser  and	select
       "settings", then select "View" to update the page.

       You  should  see a list of items with the descriptions on the left side
       and the possible options or input spaces on the right.  After  changing
       something, be sure to "Save changes" to update the values in your UPS.

       If  your	 UPS  doesn't  support any read/write variables, there will be
       nothing to do on this page.

       Setting values in read/write variables can also be done from  the  com‐
       mand line with upsrw(8).

INSTANT COMMANDS
       Some UPS hardware also has provisions for performing certain actions at
       the user's command.  These include battery tests, battery  calibration,
       front  panel  tests  (beep!)  and  more.	 To access this section, do as
       above, but pick "Commands" as the function.

       If your UPS supports any instant commands, they will  be	 listed	 in  a
       chooser	widget.	  Pick the one you like and "Issue command" to make it
       happen.

       Note ‐ some dangerous commands like "Turn  off  load"  may  not	happen
       right  away.   This  is	a feature, not a bug.  The apcsmart driver and
       some others require that you send this command  twice  within  a	 short
       window  in  order to make it happen.  This is to keep you from acciden‐
       tally killing your systems by picking the wrong one.

       To actually turn off the load, you have to send the command once,  then
       send  it	 again	after 3 seconds elapse but before 15 seconds pass.  If
       you do it too quickly or slowly, you have to wait at  least  3  seconds
       but not 15 seconds again.

       You  can	 also  invoke  instant	commands  from	the  command line with
       upscmd(8).

ACCESS CONTROL
       upsset will only talk to upsd(8) servers that have been defined in your
       hosts.conf(8).	If  it	complains  about  "Access  to that host is not
       authorized", check your hosts.conf first.

SECURITY
       upsset will not run until you convince it that your CGI	directory  has
       been  secured.	This is due to the possibility of someone using upsset
       to try password combinations against your upsd(8) server.

       See the example upsset.conf file for more information  on  how  you  do
       this.   The short explanation is ‐ if you can't lock it down, don't try
       to run it.

FILES
       hosts.conf(5)

SEE ALSO
   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

				Sat Aug 31 2002			 upsset.cgi(8)
[top]

List of man pages available for Mandriva

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net